  • GCK低压抽出式开关柜.jpg

GCK low voltage withdrawable switchgear


Category: Low-voltage Switchgear

Description: It mainly produces all kinds of high, medium and low voltage switchgear. Since its establishment, it has developed rapidly with the support of the majority of users. At present, it has a number of advanced machinery and equipment production lines and a scientific research and management team composed of middle and senior talents with rich experience and strong technical force. Technological level and product quality, to better serve our customers.

Keywords: high-voltage switchgear, medium-voltage switchgear, low-voltage switchgear, box-type substation, integrated distribution station


Product Details

Product Overview

GCK series low-voltage withdrawable switchgear is suitable for generators, metallurgy, petrochemical, light industry production lines, ports, buildings, hotels and other places as AC three-phase four-wire or five-wire, voltage 380V, 50Hz power system distribution For electric and motor control, if equipped with intelligent instruments and switches, it can be connected to the upper network through the communication interface to realize intelligent management.

This product complies with GB7251 and IE439-1 and NEMAICS-2-322 (American Electrical Standards Institute) and other standards.

Model Description

 

GCK low-voltage withdrawable switchgear

 

Use ambient conditions

The ambient air temperature should not be higher than +40°C, not lower than -5°C, and the average temperature within 24 hours should not be higher than +35°C.

The relative humidity of the surrounding air should not exceed 50% at the highest temperature of +40°C, and a larger relative humidity is allowed at lower temperatures, such as 90% at +20°C. Occasional condensation effects.

The altitude does not exceed 2000M

When the device is installed, the inclination from vertical should not exceed 5%, and the whole group of cabinets should be arranged relatively flat.

The device should be installed in a place where there is endless strong vibration and shock and where the electrical components are not enough to be corroded.

This device is suitable for transportation and storage in the following temperature range: -25°C to +55°C, not exceeding +70°C for a short period of time (24 hours).

Main technical parameters

 

GCK low-voltage withdrawable switchgear

 

Structural Features

The skeleton is composed of C-shaped, C-shaped beams and angular connectors with pressure ribs. The cabinet body has high strength. The angular connectors can make the cabinet rack installation simple, convenient and effective. The cabinet rack installation is simple, convenient and effective. The magnetic circuit of the cabinet frame is disconnected: the installation hole of E=25mm modulus is used on the cabinet frame, which is convenient for installation and flexible.

The functional unit is designed according to the modular structure, the effective device installation height is 1800mm, and the drawer unit module is 200mm

The cabinet is divided into horizontal bus room, vertical bus room, functional unit room and cable room, all of which are isolated by steel plates. The functions of each unit are relatively independent and strictly separated to ensure safe use.

GCK low-voltage withdrawable switchgear

 

The functional units of the feeder cabinet are of a drawer type, and the vertical busbar is located on the left side of the rear of the cabinet. Each functional unit is connected to the vertical busbar in parallel, and the same functional units connected by plug-ins are interchangeable. The insertion and extraction of functional units will not affect the normal power supply of adjacent functional units.

Drawers higher than 400mm are equipped with upper and lower propulsion structures. The functional unit and the main switch cable room are mechanically interlocked. The door cannot be opened when the main switch is on, and the door can only be opened when the main switch is off.

The key components such as the inner beam of the cabinet, the unit partition, the component mounting plate and the mounting support are all made of aluminum-zinc cladding, which can enhance its anti-corrosion ability and mechanical strength. Cabinet doors are electrostatically sprayed with epoxy powder. The protection level of the cabinet reaches IP30, which ensures the safety, maintenance, inspection, monitoring, maintenance and experiment of the staff.

GCK low-voltage withdrawable switchgear

 

Dimensions and Mounting Dimensions

 

 GCK low-voltage withdrawable switchgear

 

 

GCK low-voltage withdrawable switchgear

 

Installation and maintenance

1. When the device arrives at the destination, first check whether the packing box is complete. If the device is not installed immediately, it should be stored in a dry and clean place.

2. The device is recommended to be installed away from the wall, the installation base plane should be flat, the horizontal error of the foundation channel steel is 1/1000, and the total length deviation is 3mm.

3. It is recommended to use grade 8.8 and tension washer for the bolt fixing method of the conductive part used, and the recommended tightening torque is listed in the attached table

4. After the cable is connected, the bottom of the device should be closed to prevent small animals from crawling into the cabinet and causing a short circuit accident.

5. Before the device is put into operation, the following inspections and experiments shall be carried out:

A. Check whether the electrical equipment and wiring inside the switch cabinet meet the requirements of the drawing, whether the wire ends are marked with numbers, and whether the wiring is neat and firm.

B. Check whether the installed electrical equipment is in good contact and whether it meets the technical conditions of the electrical equipment itself.

C. Whether the main contacts of the main electrical appliances are reliable and accurate.

D. Check the reliability of mechanical interlocks and electrical interlocks.

E. Check whether the pull-out components are flexible and the contact is good, and there should be no jamming or excessive operating force.

F. Check whether the insulation resistance of the main circuit and the control circuit meets the specified requirements, and check and test whether the grounding device of the switch cabinet is reliable.

G. Check and test whether the meter and relay used are correct.

H. Drawers of the same specification should be easily interchangeable without jamming and collision.

 

GCK low-voltage withdrawable switchgear

 

Transport and storage of the unit

A. The device can be hoisted or transported by forklift.

B. The device must not be tilted and subjected to severe vibration.

C. If the device needs to move a small distance when it is installed in place, it can be pryed on the four corners of the chassis.

D. It is not allowed to disassemble electrical products and components in the device.

E. Rain and damp should be prevented, and the ambient temperature should be in accordance with the relevant regulations of this sample.

Product kits

The switchgear comes with packing list, product certificate, instruction manual, and necessary diagrams

Paper, random accessories include door keys and spare parts provided according to the matching list.

Ordering Instructions

Users should provide the following information:

Main wiring diagram scheme and secondary schematic diagram:

Switchgear arrangement diagram, distribution room floor plan:

Surface color of switchgear cabinet:

Detailed specifications of main electrical components:

Other special requirements.

Main board scheme

 

GCK low-voltage withdrawable switchgear

 

 

GCK low-voltage withdrawable switchgear

 

 

GCK low-voltage withdrawable switchgear

 

 

GCK low-voltage withdrawable switchgear